Healthcare MEP contractor for imaging and clinical rooms

Imaging equipment has MEP demands that a standard scope does not cover: dedicated earthing, EMI-aware cable routes, medical gases, and HVAC that holds tight temperature and humidity limits. We deliver them in step with the shielding, so every penetration is planned once.

Overhead services routed through a new building: pipework, cable tray and conduit

Why MEP and shielding belong together

Healthcare MEP for imaging rooms is mechanical, electrical and plumbing work engineered around the equipment and its shield. The equipment sets dedicated requirements: earthing, power, cooling and humidity limits, medical gas outlets and cable routes that avoid electromagnetic interference. The shield sets the rule for everything that crosses it: in an MRI suite pipes pass through waveguides, ducts through honeycomb waveguide vents and electrical cables through RF filters, while in a lead-lined room each crossing needs a lead-backed sleeve or box. EGC plans every penetration on the drawings before anything is cut, in step with the shielding, then installs, pressure-tests and balances the services to the specified conditions and hands over as-built drawings and test records with the room. Doing both under one contractor means the details that normally fall between packages are drawn once instead of being found on site.

When shielding and MEP are separate packages, those crossings are discovered late and fixed on site. Under one contractor they are drawn once, before anything is cut.

Where it is used

  • MRI suites
  • CT and PET-CT rooms
  • X-ray rooms
  • Controlled clinical environments

What we deliver

  • Medical gas pipeline systems: oxygen, medical air and vacuum
  • Electrical infrastructure and earthing for imaging equipment
  • EMI/RFI-aware cable routing and containment
  • HVAC design and installation for controlled clinical environments
  • Coordination with OEM installation teams during commissioning
  • MEP shop drawings and as-built documentation

From our sites

  • Overhead services in a new building, with red sprinkler pipework above the ceiling line
    Overhead services in a new building, with red sprinkler pipework above the ceiling line
  • Painted steel hangers supporting services below the slab
    Painted steel hangers supporting services below the slab
  • Electrical distribution panel with labelled, colour-coded wiring
    Electrical distribution panel with labelled, colour-coded wiring

What crosses the shield, and how

What crosses the shield, and how
ServiceIn an MRI suiteIn a lead-lined room
Pipes (medical gases, water)Pass through a waveguide in the RF shieldPass through a lead-backed sleeve
Air ductsPass through a honeycomb waveguide vent in the RF shieldCross through a lead-lined section or baffle
Power and data cablesEnter through RF filters, routed to the manufacturer’s requirementsRun in lead-backed boxes and containment
Quench pipe (MRI helium vent)Routed to the outside to the manufacturer’s specification, and kept clearNot applicable
EarthingDedicated earthing as the manufacturer specifiesEarthing to the equipment specification

Who specifies what, and who builds it

Who specifies what, and who builds it
WhoWhat they do
Equipment manufacturerStates the heat load, power, cooling, humidity, gas and earthing the equipment needs.
Building services designerDesigns the building services and plant that serve the room.
Radiation protection physicist and equipment manufacturerDefine where and how services may cross the shield.
EGCPlans every penetration with the shielding, installs, pressure-tests and balances the services, and hands over as-built drawings and test records.

How we deliver it

  1. Agree loads and routes

    We take heat loads, power and service requirements from the OEM and agree routes with the design team.

  2. Plan every penetration

    Each crossing of the shielded envelope is located, detailed and sealed on the drawings first.

  3. Install and test

    Services are installed, pressure-tested and balanced to the specified conditions.

  4. Document

    As-built drawings and test records are handed over with the room.

Planning an MRI, CT or PET-CT room?

Send us the equipment model and the site, and we will tell you what the room needs and how we would deliver it.