Radiation and magnetic shielding contractor in Saudi Arabia

We build the protective envelope around diagnostic and therapy rooms: lead lining for ionising radiation, and RF (Faraday cage) and magnetic shielding for MRI. Every layer is built to the OEM site-planning guide and the radiation protection physicist’s report.

Radiation-shielded room with lead sheet fixed to the walls, before finishes

Two different problems, two different shields

Radiation shielding contractors build the rooms that keep an imaging scanner’s energy where it belongs. In CT, PET-CT and X-ray rooms the hazard is ionising radiation, which is stopped by dense material, usually lead; a radiation protection physicist calculates how much each wall, floor, ceiling, door and window needs and records it in a shielding report. In an MRI suite the problem is different: the room is shielded from radio-frequency interference by a continuous conductive envelope, usually copper, aluminium or galvanised steel, and sometimes the magnet’s fringe field is contained with steel plate, as the manufacturer’s site-planning guide specifies. EGC builds both kinds of room from those two documents. We detail every junction, door, window and penetration on shop drawings before work starts, install the shielding with our own crews, and support the RF attenuation test or radiation survey before the room is released to the equipment manufacturer’s installation team.

The weak points are always the same: doors, windows, junctions and every pipe, duct and cable that crosses the shield. That is why we coordinate shielding with the door and healthcare MEP packages instead of treating it as a separate trade.

Where it is used

  • MRI suites
  • CT rooms
  • PET-CT suites
  • X-ray and fluoroscopy rooms
  • Nuclear medicine rooms
  • Radiation therapy vaults

What we deliver

  • MRI suites with RF (Faraday cage) and magnetic shielding
  • Lead-lined walls, ceilings and floors for CT, PET-CT and X-ray rooms
  • Nuclear medicine rooms and radiation therapy vaults
  • Lead-glass viewing windows and RF windows
  • Continuous-lining details at junctions, boxes and penetrations
  • Retrofit shielding for existing diagnostic rooms

From our sites

  • Lead-lined room under construction, with metal studs and a ladder
    Lead-lined room under construction, with metal studs and a ladder
  • Lead-lined wall with a steel frame and a service opening
    Lead-lined wall with a steel frame and a service opening
  • Sliding door with radiation warning signs and a card reader beside it
    Sliding door with radiation warning signs and a card reader beside it

MRI and CT shielding compared

MRI and CT shielding compared
MRI suiteCT, PET-CT and X-ray rooms
What it controlsRadio-frequency interference getting in, and the magnet’s fringe field reaching outsideIonising radiation (X-rays, or the 511 keV photons from PET tracers) escaping the room
Typical materialA continuous conductive envelope of copper, aluminium or galvanised steel, plus steel plate where the manufacturer specifies itDense material, usually lead sheet or lead-lined board
Who sets the amountThe manufacturer’s site-planning guideThe radiation protection physicist’s shielding report
Usual weak pointsDoor, window, waveguides and filters, any unsealed seamDoor, viewing window, junctions, boxes and penetrations
How it is checkedRF attenuation testRadiation survey once the room is built

Who specifies what, and who builds it

Who specifies what, and who builds it
WhoWhat they do
Equipment manufacturerPublishes the site-planning guide for the exact model: room size, RF and fringe-field limits, services and penetrations.
Radiation protection physicistCalculates the shielding each surface needs and issues the shielding report.
Hospital design team and main contractorProvide the structure, the layout and the programme the shielding has to fit into.
EGCReads both documents together, builds and inspects the shielding, and supports RF and radiation testing before handover.

How we deliver it

  1. Review the specification

    We read the OEM site-planning guide and the physicist’s shielding report side by side and resolve conflicts before drawings are issued.

  2. Detail the envelope

    Shop drawings show every lining layer, seam, junction and penetration, so nothing is improvised on site.

  3. Build and inspect

    Our own crews install the shielding, and continuity is checked before finishes close it in.

  4. Test and hand over

    We support the RF attenuation test or the radiation survey, then release the room to the OEM installation team.

Planning an MRI, CT or PET-CT room?

Send us the equipment model and the site, and we will tell you what the room needs and how we would deliver it.